In today's industrialized society, power supply is closely related to the production of industrial facilities, the operation of national defense and military facilities, the development of scientific and technological research, and the normal conduct of people's lives. With the improvement of people's living standard, the demand for energy is increasing, so the transformer load increases with the increase of accidents. Transformer accident is harmful to the safe operation of power grid. so it is necessary to find fault and eliminate the fault in time, so that the power grid can be unblocked.
The operation condition of oil immersed transformer has direct influence on the power supply quality of the whole power system. In the actual operation, due to various factors, the transformer will inevitably appear in the course of a variety of faults. These failures lead to power outages, heavy equipment, equipment outages, and even major power accidents. Therefore, it is necessary to make a scientific analysis of the oil immersed transformer fault.
1.Fault analysis of abnormal sound of transformer
When the transformer is in normal operation, its sound mainly comes from two aspects: the transformer body and the cooling system. The vibration of iron core caused by magnetic and magnetic leakage of silicon steel sheet is the main cause of vibration of transformer body. When the following faults occur, the transformer will produce abnormal sound:
(1) The core bolt of the iron core is not firmly fixed, which will lead to loose core and cause irregular vibration between the silicon steel sheets, thus causing strong and uneven noise.
(2) When the winding flashover discharge or the grounding wire of the iron core is broken, it will cause the iron core to discharge the high voltage outer shell, and cause the discharge sound inside the transformer.
(3) A few parts of transformer is not firmly fixed, within the transformer there is iron tapping sound.
(4) In the case of light load or empty load, some of the end of the laminated silicon steel sheet will vibrate, and there will be a mosquito flapping sound inside the transformer.
(4) In the case of light load or empty load, some of the end of the laminated silicon steel sheet will vibrate, and there will be a mosquito flapping sound inside the transformer.
(5) If there is a breakdown in the transformer. There will be a big and small discharge sound.
2. Analysis of Oil immersed transformer oil level and oil temperature abnormal fault
(1) The oil level of transformer is too high or too low
The oil level of the transformer is affected by the following factors: a. internal oil content b.oil temperature c.transformer load d.ambient temperature e.transformer sealing and so on. Oil pillow volume is generally about 10% of the transformer volume. If the oil level is too high, easy to cause oil spill. If the oil level is too low, the transformer leads to the wiring part to be exposed to the air, which reduces the insulation effect and may cause an internal short circuit. At the same time, as the oil and air contact area becomes larger, the insulation strength of the oil decreases rapidly. In case of power failure or low temperature in winter, the oil level will drop rapidly, triggering the action of light gas relay. From the above analysis, we can see that the transformer must keep the normal oil level in operation. Operators must always check the level of oil level gauge, and take corresponding measures to maintain normal oil level, to ensure the safe operation of the transformer.
(2) Oil leakage fault of transformer
Transformer oil has a strong penetration force, usually after the infiltration of oil seal for poor sealing or welding point welding two categories.
To achieve the prevention of transformer oil, first, need to carefully check the record of the original data, and experience of all seal welds and check the transformer oil, according to find all leaks; second, the leakage point welding in time; third, material, try to choose the installation process of high quality seals and improved transformer.
(3) oil temperature continues to rise
Transformer in the daily operation of the oil temperature rising phenomenon, indicating that the transformer internal problems. The main reason is the iron core overheating or winding turn to turn short-circuit. The bolt clamping core insulation or eddy current caused by the destruction of the core overheating. The eddy current will keep the core temperature high for a long time, resulting in iron loss and rising oil temperature. Through that bolt insulation was destroyed will cause overheating of the screw. When the temperature rises to the extent that the iron core is fused together, the transformer should be cut off immediately so as to avoid a major accident such as fire or explosion.
3. Analysis of oil immersed transformer circuit fault
(1) Insulation material damage caused by failure
First, when the transformer is installed, the cover is checked and exposed to air, causing moisture. The vacuum treatment is not complete before oiling, so that the moisture is concentrated around the insulating parts. Second, maybe due to equipment manufacturing cycle is short, if the insulation factory is not fully dry, insulating paper and board out after running for a period of time, water absorption water, resulting in low voltage winding of the transformer insulation performance is reduced, resulting in DC leakage current increases. Third, poor sealing, easy to cause winding insulation part of the damp. Fourth, if the volume of hydrogen and carbon monoxide in the transformer oil is relatively high, the adsorption of the gas produced by the solid insulating material or stainless steel in the manufacturing process should be taken into account.
Insulation damp is one of the main causes of insulation failure, so it is necessary to strengthen the prevention and supervision work, do a good job of checking the insulation effect of the important components of the transformer, and find out and eliminate the fault as soon as possible. When installing and overhauling transformers, minimize the time that the transformer is exposed to the atmosphere. In the production of transformers, the standard of drying process should be strictly carried out, and the moisture content of insulating paper (sheet) shall be controlled within 0.3. The leakage points of the transformer body and accessories should be treated in time to avoid infiltration of moisture into the transformer. Improve design and manufacturing processes, and monitor material selection.
(2)Influence of discharge fault on transformer insulation
The influence of the discharge on the transformer insulation is divided into two kinds of damage: a. the discharge particle directly impacts the insulation and makes the insulation breakdown. b. ozone and nitrogen oxides generated by the discharge, chemical corrosion, insulation components, and finally lead to thermal breakdown.
The main form of aging of insulating materials is a. the damage of chemical structure of insulating materials is caused by partial discharge. b.the thermal effect of the discharge point causes the thermal cracking of the insulation and accelerates the aging process. c.the ozone and nitrogen oxides generated by the discharge process corrode the insulator by chemical reaction and weaken the insulation performance. (d.during the discharge process, the transformer oil decomposes to produce bubbles, which make it difficult to heat the solid insulation and cause damage to the solid insulation.
Within the insulation structure, the phenomenon of non - penetrating discharge at the edge of the hole is known as partial discharge under the action of voltage. The reason is: a hole or cavity in transformer oil gas, gas of low dielectric constant reduces the compressive strength of insulating material, causing the discharge gap between the transformer oil; processing net, will make the bubble in the transformer oil caused by discharge; discharge between metal parts or conductive contact will cause the bad. Although the energy intensity of partial discharge is not large, but the potential harm can not be overlooked, if long-term partial discharge will cause breakdown or damage to equipment, is a serious safety hazard.
(4)analysis of automatic trip fault
In case of standby transformer, if the main transformer is automatic tripping, the working transformer should be deactivated immediately, and the standby transformer can be used at the same time. To check the cause of automatic tripping of the transformer. If internal trouble is found during inspection, internal inspection should be carried out immediately. If it is found that the tripping is caused by differential protection, the electrical equipment in the differential protection range shall be checked and power transmission shall be carried out after troubleshooting.
4.Epilogue
According to the above fault analysis, the staff should monitor the sound, the oil level and the circuit condition of the transformer. According to the characteristics of the relevant fault, make timely and ready analysis, and quickly formulate the corresponding repair plan, to repair the fault at the fastest speed. In short, when the oil immersed transformer after the failure, the staff should do the analysis according to the real-time fault situation, and formulate the corresponding countermeasures, eliminating the trouble in the bud, to ensure the safe and stable operation of transformer.